Communication Protocol
119 - 144
Function instruction
Address
definition
Data meaning instruction
R/W
characteristics
Setting frequency
3001H
Range: 0.00Hz~P00.03
R
Bus voltage
3002H
Range: 0~1200V
R
Output voltage
3003H
Range: 0~1200V
R
Output current
3004H
Range: 0.0~5000.0A
R
Operation speed
3005H
Range: 0~65535 RPM
R
Output power
3006H
Range: -300.0~300.0%
R
Output torque
3007H
Range: -250.0~250.0%
R
Close loop setting
3008H
Range: -100.0%~100.0%
R
Close loop feedback
3009H
Range: -100.0%~100.0%
R
Input IO state
300AH
Range: 0000~00FF
R
Output IO state
300BH
Range: 0000~00FF
R
AI 1
300CH
Range: 0.00~10.00V
R
AI 2
300DH
Range: 0.00~10.00V
R
AI 3
300EH
Range: 0.00~10.00V
R
AI 4
300FH
Reserved
R
Read high speed pulse 1 input
3010H
Range: 0.00~50.00kHz
R
Read high speed pulse 2 input
3011H
Reserved
R
Read current stage of the
multi-step speed
3012H Range:
0~15
R
External length
3013H
Range: 0~65535
R
External counting value
3014H
Range: 0~65535
R
Torque setting
3015H
-300.0~300.0% (Unit: 0.1% )
R
Inverter code
3016H
R
Fault code
5000H
R
R/W characteristics means the function is with read and write characteristics. For example, “communication
control command” is writing characteristic and control the inverter with writing command (06H). R
characteristic can only read other than write and W characteristic can only write other than read.
Note:
when operate on the inverter with the table above, it is necessary to enable some parameters. For
example, the operation of running and stopping, it is necessary to set P00.01 to communication running
command channel and set P00.02 to MODBUS communication channel. And when operate on “PID
reference”, it is necessary to set P09.00 to “MODBUS communication setting”.
The encoding rules for device codes (corresponds to identifying code 2103H of the inverter)
Code high 8 bit
Meaning
Code low 8 bit
Meaning
01 ControlVIT
0x0d CV10
inverters
0x06 CV30
inverters
0x0c CV50
inverters
Note:
the code is consisted of 16 bit which is high 8 bits and low 8 bits. High 8 bits mean the motor type
series and low 8 bits mean the derived motor types of the series. For example, 0110H means CV50 inverters.
9.5.3 Fieldbus ratio values
The communication data is expressed by hex in actual application and there is no radix point in hex. For
example, 50.12Hz can not be expressed by hex so 50.12 can be magnified by 100 times into 5012, so hex
1394H can be used to express 50.12.
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...