42 - 144
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P01.22
Waiting time
of restart after
power off
The function determines the waiting time before the
automatic running of the inverter when powering off and
then powering on.
Setting range: 0.0~3600.0s (valid when P01.21=1)
1.0 s
○
P01.23 Start delay time
The function determines the brake release after the running
command is given, and the inverter is in a stand-by state
and wait for the delay time set by P01.23
Setting range: 0.0~60.0s
0.0 s
○
P01.24
Delay time of
the stop speed
Setting range: 0.0~100.0 s
0.0 s
●
P01.25
0 Hz output
selection
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
0
●
P02 Group Motor 1
P02.01
Rated power of
motor 1
0.1~500.0kW
Depends
on model
◎
P02.02
Rated frequency
of motor 1
0.01Hz~P00.03 (the Max. frequency)
50.00 Hz
◎
P02.03
Rated speed
of motor 1
1~36000rpm
Depends
on model
◎
P02.04
Rated voltage
of motor 1
0~1200V
Depends
on model
◎
P02.05
Rated current
of motor 1
0.8~6000.0A
Depends
on model
◎
P02.06
Stator resistor
of motor 1
0.001~65.535
Ω
Depends
on model
○
P02.07
Rotor resistor
of motor 1
0.001~65.535
Ω
Depends
on model
○
P02.08
Leakage
inductance of
motor 1
0.1~6553.5mH
Depends
on model
○
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...