Communication Protocol
111 - 144
9.4 RTU command code and communication data illustration
9.4.1 RTU mode
9.4.1.1Command code: 03H
03H
(
correspond to binary 0000 0011), read N words
(
Word
)
(the Max. continuous reading is 16 words)
Command code 03H means that if the master read data from the inverter, the reading number depends on the
“data number” in the command code. The Max. Continuous reading number is 16 and the parameter address
should be continuous. The byte length of every data is 2 (one word). The following command format is
illustrated by hex (a number with “H” means hex) and one hex occupies one byte.
The command code is used to read the working stage of the inverter.
For example, read continuous 2 data content from 0004H from the inverter with the address of 01H (read the
content of data address of 0004H and 0005H), the frame structure is as below:
RTU master command message (from the master to the inverter)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR 01H
CMD 03H
High bit of the start address
00H
Low bit of the start address
04H
High bit of data number
00H
Low bit of data number
02H
CRC low bit
85H
CRC high bit
CAH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 between START and END is to provide at least the time of 3.5 bytes as the leisure time and
distinguish two messages for the avoidance of taking two messages as one message.
ADDR
= 01H means the command message is sent to the inverter with the address of 01H and ADDR
occupies one byte
CMD
=03H means the command message is sent to read data from the inverter and CMD occupies one byte
“Start address”
means reading data from the address and it occupies 2 bytes with the fact that the high bit is
in the front and the low bit is in the behind.
“Data number”
means the reading data number with the unit of word. If the “start address’ is 0004H and the
“data number” is 0002H, the data of 0004H and 0005H will be read.
CRC
occupies 2 bytes with the fact that the high bit is in the front and the low bit is in the behind.
RTU
slave response message (from the inverter to the master)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR 01H
CMD 03H
Byte number
04H
Data high bit of address 0004H
13H
Data low bit of address 0004H
88H
Data high bit of address 0005H
00H
Data low bit of address 0005H
00H
CRC CHK low bit
7EH
CRC CHK high bit
9DH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...