Communication Protocol
115 - 144
ASCII master command message (the command
sent by the master to the inverter)
ASCII slave response message (the message
sent by the inverter to the master)
High bit of write data
‘0’
High bit of write data
‘0’
‘0’
‘0’
Low bit of write data
‘0’
Low bit of write data
‘0’
‘4’
‘4’
High bit of data content
‘1’
High bit of data content
‘1’
‘3’
‘3’
Low bit of data content
‘8’
Low bit of data content
‘8’
‘8’
‘8’
LRC CHK Hi
‘5’
LRC CHK Hi
‘5’
LRC CHK Lo
‘9’
LRC CHK Lo
‘9’
END Hi
CR
END Hi
CR
END Lo
LF
END Lo
LF
9.4.2.3 Command code: 08H (0000 1000), diagnose function
Meaning of sub function code:
Sub function code
Instruction
0000
Return inquiry message data
For instance: carry out circuit detection on drive address 01H, the content of inquiry message word string is
the same with response message word string, its format is listed as below:
ASCII master command message (the command
sent by the master to the inverter)
ASCII slave response message (the message
sent by the inverter to the master)
START
‘:’
START
‘:’
ADDR
‘0’
ADDR
‘0’
‘1’
‘1’
CMD
‘0’
CMD
‘0’
‘8’
‘8’
High bit of write data address
‘0’
High bit of write data address
‘0’
‘0’
‘0’
Low bit of write data address
‘0’
Low bit of write data address
‘0’
‘0’
‘0’
High bit of data content
‘1’
High bit of data content
‘1’
‘2’
‘2’
Low bit of data content
‘A’
Low bit of data content
‘A’
‘B’
‘B’
LRC CHK Hi
‘3’
LRC CHK Hi
‘3’
LRC CHK Lo
‘A’
LRC CHK Lo
‘A’
END Hi
CR
END Hi
CR
END Lo
LF
END Lo
LF
9.4.2.4 Command code: 10H, continuous writing function
Command code 10H means the master write data to the inverter, the number of data being written is
determined by the command “data number”, the max. number of continuous writing is 16 words.
For instance: Write 5000 (1388H) to 0004H of the inverter whose slave address is 02H, write 50 (0032H) to
0005H of the inverter whose slave address is 02H, then the structure of this frame is listed as below:
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...