Function Parameters
65
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping frequency,
the inverter will run at the edge of the jumping frequency.
The inverter can avoid the mechanical resonance point by
setting the jumping frequency. The inverter can set three
jumping frequencies. But this function will be invalid if all
jumping points are 0.
Setting range: 0.00Hz ~P00.03 (the Max. frequency)
0.00 Hz
○
P08.10
Jumping
frequency range
1
0.00 Hz
○
P08.11
Jumping
frequency 2
0.00 Hz
○
P08.12
Jumping
frequency range
2
0.00 Hz
○
P08.13
Jumping
frequency 3
0.00 Hz
○
P08.14
Jumping
frequency range
3
0.00 Hz
○
P08.15 Traverse range This function applies to the industries where traverse and
convolution function are required such as textile and
chemical fiber.
The traverse function means that the output frequency of
the inverter is fluctuated with the set frequency as its center.
The route of the running frequency is illustrated as below, of
which the traverse is set by P08.15 and when P08.15 is set
as 0, the traverse is 0 with no function.
Traverse range: The traverse running is limited by upper
and low frequency.
The traverse range relative to the center frequency:
traverse range AW
=
center frequency
×
traverse range
P08.15.
Sudden jumping frequency
=
traverse range AW
×
sudden
jumping frequency range P08.16. When run at the traverse
frequency, the value which is relative to the sudden jumping
frequency.
The raising time of the traverse frequency: The time from
the lowest point to the highest one.
The declining time of the traverse frequency: The time from
the highest point to the lowest one.
The setting range of P08.15: 0.0~100.0% (relative to the set
frequency)
0.0 %
○
P08.16
Sudden jumping
frequency range
0.0 %
○
P08.17
Traverse boost
time
5.0 s
○
P08.18
Traverse
declining time
5.0 s
○
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...