Function Parameters
55
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.34
Upper limit of
AI1
input value, the inverter will count at the minimum or
maximum one.
When the analog input is the current input, the
corresponding voltage of 0~20mA is 0~10V.
In different cases, the corresponding rated value of 100.0%
is different. See the application for detailed information.
The figure below illustrates different applications:
Input filter time
: this parameter is used to adjust the
sensitivity of the analog input. Increasing the value properly
can enhance the anti-interference of the analog, but
weaken the sensitivity of the analog input
Note:
Analog AI1 and AI2 can support 0~10V or 0~20mA input,
when AI1 and AI2 selects 0~20mA input, the corresponding
voltage of 20mA is 5V. AI3 can support an input of -10V~+10V.
The setting range of P05.32: 0.00V~P05.34
The setting range of P05.33: -100.0%~100.0%
The setting range of P05.34: P05.32~10.00V
The setting range of P05.35: -100.0%~100.0%
The setting range of P05.36: 0.000s~10.000s
The setting range of P05.37: 0.00V~P05.39
The setting range of P05.38: -100.0%~100.0%
The setting range of P05.39: P05.37~10.00V
The setting range of P05.40: -100.0%~100.0%
The setting range of P05.41: 0.000s~10.000s
The setting range of P05.42: -10.00V~P05.44
The setting range of P05.43: -100.0%~100.0%
The setting range of P05.44: P05.42~P05.46
The setting range of P05.45: -100.0%~100.0%
The setting range of P05.46: P05.44~10.00V
The setting range of P05.47: -100.0%~100.0%
The setting range of P05.48: 0.000s~10.000s
10.00 V
○
P05.35
Correspon ding
setting of the
upper limit of AI1
100.0 %
○
P05.36
AI1 input filter
time
0.100 s
○
P05.37
Lower limit of
AI2
0.00 V
○
P05.38
Correspon ding
setting of the
lower limit of AI2
0.0 %
○
P05.39
Upper limit of
AI2
10.00 V
○
P05.40
Correspon ding
setting of the
upper limit of AI2
100.0 %
○
P05.41
AI2 input filter
time
0.100 s
○
P05.42
Lower limit of
AI3
-10.00 V
○
P05.43
Correspon ding
setting of the
lower limit of AI3
-100.0 %
○
P05.44
Middle value of
AI3
0.00 V
○
P05.45
Correspon ding
middle setting of
AI3
0.0 %
○
P05.46
Upper limit of
AI3
10.00 V
○
P05.47
Correspon ding
setting of the
upper limit of AI3
100.0 %
○
P05.48
AI3 input filter
time
0.100 s
○
P05.49
HDI high-speed
pulse input
The function selection when HDI terminals is high-speed
pulse input
0: Frequency setting input
, frequency setting source
1: Counter input
, high-speed pulse counter input terminals
2: Length counting input
, length counter input terminals
0
◎
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...