8. SPECIFICATIONS
IMSRM02-E6
97
Open collector output:
Load voltage:
12 to 24 V DC
Maximum load current:
100 mA
Leak current when OFF:
0.1 mA or less
Maximum voltage drop at ON: 2.4 V or less (At a load current of 100 mA)
0.7 V or less (At a load current of 10 mA)
The minus terminals of the output with the two channels specification are
internally contacted in common.
Specify when ordering
Temperature alarm function
Number of alarms:
2 points
Alarm types:
Deviation high alarm
Deviation low alarm
Deviation high/low alarm
Deviation band alarm
Deviation high alarm (with alarm hold)
Deviation low alarm (with alarm hold)
Deviation high/low alarm (with alarm hold)
Specify when ordering (Alarm action is specified for the PCP module.)
Setting range:
-span to +span:
Deviation high alarm, Deviation low alarm,
Deviation high alarm (with alarm hold),
Deviation low alarm (with alarm hold)
0 to span:
Deviation high/low alarm, Deviation band alarm,
Deviation high/low alarm (with alarm hold)
Same as input range: Process high alarm, Process low alarm,
Process high alarm (with alarm hold),
Process low alarm (with alarm hold)
Specify when ordering (Alarm action is specified for the PCP module.)
Setting resolution:
Same as input resolution
Alarm output:
This module outputs alarm status to the PCP module as data.
Alarm output (Only for TIO-A type) [option]
Number of outputs:
1 point
Select any of temperature alarm output 1 (ALM1), temperature alarm output 2
(ALM2), heater break alarm output (HBA) or loop break alarm output (LBA).
Relay contact output:
Rating:
250 V AC 24 V DC 2 A (Resistive load)
Electrical life: 300,000 times or more (Rated load)
Contact type: 1a contact
Minimum switching voltage and current: 5 V DC 1 mA
Isolation method:
Photocoupler isolation
Process high alarm
Process low alarm
Process high alarm (with alarm hold)
Process low alarm (with alarm hold)
Deviation high alarm (with alarm re-hold)
Deviation low alarm (with alarm re-hold)
Deviation high/low alarm (with alarm re-hold)