3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
29
Input function
z
z
z
z
Digital input (PCP-B)
For digital input, memory area selection, control RUN/STOP selection or alarm interlock release
specifying can be performed. In addition, any of the following combinations of functions is available
for digital input.
•
Type 1: Memory area selection (8 areas selection)
•
Type 2: Combination of control RUN/STOP selection and memory area selection
(4 areas selection)
•
Type 3: Combination of control RUN/STOP selection, alarm interlock release and memory area
selection (2 areas selection)
After the contact is closed, it takes a short time until the action of this device is actually
selected. Therefore, pay attention to this delay time if the device is used together with a
sequencer, etc.
External power supply (24 V DC) is required for digital input.
Memory area selection (Type 1)
The memory area (control area) can be selected depending on the open or close state of terminal
numbers 7 to 10. Select the memory area by configuring an external contact circuit or using a contact
output signal from the sequencer, if necessary.
Control area
Terminal Nos.
1
2
3
4
5
6
7
8
7 - 8
−
×
−
×
−
×
−
×
7 - 9
−
−
×
×
−
−
×
×
7 - 10
−
−
−
−
×
×
×
×
−
: Open
×
: Close
Control RUN/STOP selection, memory area selection (Type 2)
Selection can be performed depending on the open or close state of terminal numbers 7 to 10.
Control area
Terminal Nos.
1
2
3
4
7 - 8
−
×
−
×
7 - 9
−
−
×
×
−
: Open
×
: Close
Contact opened: Control STOP Contact closed: Control RUN
7
8
9
10
DI1
DI2
DI3
7
8
9
10
DI1
DI2
DI3