3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
40
(3) Alarm function
One TIO module is provided with two alarm points as standard. Each alarm status is output to the
PCP module from the TIO module as data.
The respective alarm (ALM1/ALM2) can be output independently for each channel by connecting the
DO module. (
See P. 83.)
For TIO-A/E/H/R type modules, an alarm can be output from each module (option).
For details on outputting alarms, see
3.7 DO Module (P. 46)
,
and for details on setting
alarms, see the
Operation Panel Instruction Manual (OPM: IMSRM03-E
, OPL-A:
IMSRM11-E
, OPM [Z-191 specifications]: IMSRM21-E
, OPM-H [Z-191
specifications]: IMSRM26-E
)
,
and
the
Communication Instruction Manual
Supplementary Information Initialize Settings (Extended Communications)
(IMSRM07-E
)
.
(4) Alarm output function (Option)
An alarm can be output from the TIO module itself (only for the TIO-A types).
•
Number of output points: One point (relay contact output)
•
Output type : Select any of temperature alarm output (ALM1), temperature alarm output (ALM2),
heater break alarm output (HBA) * or loop break alarm output (LBA) *.
* Only TIO-A can be selected.