6. IN CASE OF TROUBLE
IMSRM02-E6
73
In this instrument, even if a function module is detached, the operation of the other channels
can be continued as before.
After mounting the normally operating module, set the channel used by this module to the
Normal
mode. This operation causes the previously used temperature set value, PID
constants, etc. to be transmitted from the PCP module, and it is possible to use the module as
before.
For more details of the operation methods, etc., see the
Operation Panel
Instruction Manual (OPM: IMSRM03-E
, OPL-A: IMSRM11-E
, OPM [Z-
191 specifications]: IMSRM21-E
, OPM-H [Z-191 specifications]: IMSRM26-
E
)
, and the
Communication Instruction Manual Supplementary Information
Initialize Settings (Extended Communications) (IMSRM07-E
)
.
Mother block
PCP module
Used
Used
Used
Unused
Used
used
Be careful not to remove the module without first setting this channel to the
Unused
mode,
otherwise a failure will be output from the PCP module. However, the FAIL lamp of the
PCP module will not light at this time.
Содержание SR Mini System
Страница 2: ...All Rights Reserved Copyright 1994 RKC INSTRUMENT INC...
Страница 110: ...104 IMSRM02 E6 MEMO...
Страница 111: ...The 1st edition Nov 1994 The 6th edition Aug 2000...