6. IN CASE OF TROUBLE
IMSRM02-E6
70
(5) DO module related
Problem
Probable cause
Solution
RUN lamp does not flash
Power line defect
Replace mother block
Power supply section defect
Replace module
CPU section breakdown
Replace module
RUN lamp stays lit
Module different from system
specifications inserted
Replace with module matching
specifications
Maximum number of linkable
units exceeded
Eliminate a module
FAIL lamp lit up
CPU section breakdown
Replace module
Specific output not operating
(RUN lamp flashing)
External operating device defect
Inspect external operating device
Output section mis-wiring, cut
line
Inspect wiring; replace as
necessary
Terminal screw loose
Tighten more
Output circuit, CPU breakdown
Replace module
Bus line defect
Replace mother block
No outputs operate
Load power not supplied
Supply power
Load power supply voltage
outside rating
Change to voltage within rating
Main CPU section breakdown
Replace PCP module
Bus line defect
Replace mother block
Specific output relay does not go
off
Output relay contacts stuck
Replace module
External operation device
recovery defect due to leakage
current at surge killer etc.
Reevaluate surge killer; reevaluate
external operating device
Output circuit, CPU breakdown
Replace module
No output relays go off
Main CPU section breakdown
Replace PCP module
Output chattering ON/OFF with
extremely short period
Terminal tightening defect
Tighten more
ON/OFF with extremely short
period
Control period too short
Change period setting
Malfunction due to excess noise
Investigate noise filter installation
Error from certain module on
Head mother block defect in error
module
Replace mother block
Module connections disconnected Check connections