8. SPECIFICATIONS
IMSRM02-E6
99
8.3 CT Module
Input
Input type:
Current transformer input (CT)
Number of inputs:
6 points
Number of common points:
3 points
(1-2 channels/common, 3-4 channels/common, 5-6 channels/common)
Isolation method:
Photocoupler isolation
Input current:
0 to 30 A:
CTL-6-P-N
0 to 100 A:
CTL-12-S56-10L-N
Specify when ordering (Current transformer is sold separately)
Accuracy of heater current measurement:
5 % of input value or
±
2 A (The value whichever is greater)
Heater break alarm function
Setting range:
0.0 to 100.0 A
Corresponding channel setting:
1 to 20 channels (Same channel can be set)
Alarm output:
This module outputs alarm status to the PCP module as data.
Self-diagnostic
Check item:
RAM check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
Reset state
General specifications
Dimensions:
24 (W)
×
96 (H)
×
100 (D) mm
Weight:
120 g