3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
28
z
z
z
z
Digital output (PCP-A and PCP-B)
The digital outputs can be optionally selected from the first alarm (ALM1), second alarm (ALM2),
heater break alarm, burnout alarm, temperature rise completion, loop break alarm, AI first alarm or AI
second alarm. For PCP-A type modules four points can be individually selected, and for PCP-B type
modules two points can be individually selected.
•
Number of outputs: 4 points (PCP-A type),
2 points (PCP-B type)
•
Output type:
Relay contact output, 1a contact (Closed at alarm occurrence)
[Rating: 250 V AC, 0.1 A (Resistive load)]
(CE/UL/CSA approved instrument: 30 V DC, 0.1 A)
Open collector output
[Load voltage: 12 to 24 V DC, Maximum load current: 0.1 A ]
If there is no heater break alarm function in the control unit (TIO-A/C/D modules provided
with CT input as option, or control unit without CT module), a heater break alarm cannot be
selected.
For details on function selection with the digital output, see the
Operation Panel
Instruction Manual (OPM: IMSRM03-E
, OPL-A: IMSRM11-E
, OPM [Z-191
specifications]: IMSRM21-E
, OPM-H [Z-191 specifications]: IMSRM26-E
)
,
and
the
Communication Instruction Manual Supplementary Information Initialize Settings
(Extended Communications) (IMSRM07-E
)
.
Open Collector Output Wiring Example
12/24 V DC
OUT4
OUT1
+
+
+
-
-
-
Load
Load