8. SPECIFICATIONS
IMSRM02-E6
103
8.6 Common Specifications
Control unit
Power supply voltage
:
100 to 120 V AC (50/60 Hz)
200 to 240 V AC (50/60 Hz)
24 V DC
Specify when ordering
Power supply voltage range:
100 to 120 V AC:
90 to 132 V AC
200 to 240 V AC: 180 to 264 V AC
24 V DC:
21.6 to 26.4 V DC
Insulation resistance:
Between power and ground terminals:
20 M
Ω
or more at 500 V DC
Between input/output and ground terminals:
20 M
Ω
or more at 500 V DC
Withstand voltage:
Between power and ground terminals:
1500 V AC for 1 minute
Between input/output and ground terminals: 1000 V AC for 1 minute
Withstand noise:
1500 V (peak to peak)
Pulse width: 1
µ
s
Rise time:
1 ns
By noise simulator
Withstand vibration:
Frequency: 5 to 9 Hz
Amplitude:
1.5 mm
Frequency: 9 to 150 Hz
Acceleration: 5.0 m/s
Sweep speed:
10 Hz/min
Vibration director: Front and back, Right and left, Up and down
(Three directions)
Vibration time:
1 hour, all directions
Power failure effect:
No influence even under power failure of 20 ms or less.
Ambient temperature range:
0 to 50
°
C
Ambient humidity range:
45 to 85 %RH (No condensation)
Operating environment
:
No corrosive gases, no large amounts of dust or particulates.
Storage temperature range:
-20 to +70
°
C
Storage humidity range:
95 %RH or less (No condensation)
Grounding resistance:
100
Ω
or less
Cooling method:
Natural cooling
Содержание SR Mini System
Страница 2: ...All Rights Reserved Copyright 1994 RKC INSTRUMENT INC...
Страница 110: ...104 IMSRM02 E6 MEMO...
Страница 111: ...The 1st edition Nov 1994 The 6th edition Aug 2000...