7. FUNCTIONS
IMSRM02-E6
86
−
Band alarm
Time
ON
OFF
ON
OFF
ON
Measured value (PV)
Measured value (PV)
Alarm set value
Alarm set value
Set value (SV)
Alarm status
Differential gap
Differential gap
(4) Alarm hold function
In the alarm hold function, the alarm function is kept invalid even if the measured value (PV) is in
the alarm range when the power is on or the operation mode is switched to Run from Stop. The
alarm function is held until the measured value (PV) goes out of the alarm state once.
−
With alarm hold action
−
Without alarm hold action
Time
Time
Alarm hold area
OFF
ON
OFF
ON
ON
Measured value (PV)
Measured value (PV)
Measured value (PV)
Measured value (PV)
Alarm
set value
Alarm
set value
Set value (SV)
Set value (SV)
Alarm status
Alarm status
Deviation
Deviation
Содержание SR Mini System