8. SPECIFICATIONS
IMSRM02-E6
94
Communication functions
z
z
z
z
RKC standard communication
Communication interface:
Based on RS-422A, EIA standard
Based on RS-232C, EIA standard
Specify when ordering
Connection method:
RS-422A: 4-wire system, multi-drop connection
RS-232C: Point-to-point connection
Protocol:
Based on ANSI X3.28 subcategory 2.5 B1
Synchronous method:
Start/stop synchronous type
Communication speed:
2400 bps, 4800 bps, 9600 bps, 19200 bps
(Selectable)
Data bit configuration:
Start bit: 1
Data bit: 7 or 8
Parity bit: Without, Odd or Even
Without for 8 data bits
Stop bit: 1
Error control:
Vertical parity (when parity bit is selected)
Horizontal parity
Data types:
ASCII 7-bit code
System setting items
Temperature alarm (first alarm and second alarm) :
Deviation high alarm
Deviation low alarm
Deviation high/low alarm
Deviation band alarm
Deviation high alarm (with alarm hold)
Deviation low alarm (with alarm hold)
Deviation high/low alarm (with alarm hold)
Specify when ordering
Alarm action of each module in the control unit is that selected here.
Temperature rise completion function:
Completion trigger range:
±
1 to
±
10
°
C (Value from main set value)
Temperature rise completion soak time: 0 to 360 minutes
General specifications
Dimensions:
48 (W)
×
96 (H)
×
100 (D) mm
Weight:
320 g
Process high alarm
Process low alarm
Process high alarm (with alarm hold)
Process low alarm (with alarm hold)
Deviation high alarm (with alarm re-hold)
Deviation low alarm (with alarm re-hold)
Deviation high/low alarm (with alarm re-hold)