8. SPECIFICATIONS
IMSRM02-E6
98
Heater break alarm function (Only for TIO-A, C and D type) [option]
Number of inputs:
1 point/control loop
Setting range:
0.0 to 100.0 A
Accuracy of heater current measurement:
5 % of input value or
±
2 A (The value whichever is greater)
Input current:
0 to 30 A:
CTL-6-P-N
0 to 100 A:
CTL-12-S56-10L-N
Current transformer:CTL-6-P-N, CTL-12-S56-10L-N (Specify when ordering)
Input rating:
Maximum current: 130 mA
Input impedance:
10
Ω
Alarm output:
This module outputs alarm status to the PCP module as data.
Loop break alarm function
Setting range:
LBA setting time:
1 to 7200 seconds
LBA deadband (LBD): Same as input range
(LBD is automatically as the value of two times of integral value after the
completion of autotuning.)
Alarm output:
This module outputs alarm status to the PCP module as data.
Self-diagnostic
Check item:
RAM check
Adjustment data check
Input value check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
All channel control outputs are turned off.
Reset state
Manual setting function
Auto/Manual transfer:
Either Auto or Manual control can be selected.
Setting range:
-5.0 to +105.0 %
Balanceless bumpless:
Balanceless bumpless transfer between Auto and Manual (both directions).
General specifications
Dimensions:
TIO-A, B, C, P: 24 (W)
×
96 (H)
×
100 (D) mm
TIO-D:
48 (W)
×
96 (H)
×
100 (D) mm
Weight:
TIO-A, B, C, P: 120 g
TIO-D:
240 g