3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
30
Control Run/Stop selection, alarm interlock release specifying and memory area selection (Type
3)
Selection or release specifying can be performed depending on the open or close state of terminal
numbers 7 to 10.
Contact opened: Memory area number 1 Contact closed: Memory area number 2
Contact closed: Alarm interlock released
Contact opened: Control STOP
Contact closed: Control RUN
Communication function
The communication interface (RS-232C or RS-422A) is used for connecting each control unit to
peripheral equipment. Communication types used are as follows depending on the peripheral
equipment to be connected.
•
Connection with dedicated operation panel
・・・・・・・
RS-422A
•
Multi-drop connection of control units
・・・・・・・・・・・
RS-422A
•
Connection with host computer
・・・・・・・・・・・・・・・・
RS-232C or RS-422A
Two types of communication protocol are available: RKC standard communication (polling/ selecting
type) and ladder communication (non-protocol type).
•
Communication with dedicated operation panel
・・・・・・・・・
RKC standard communication
•
Communication with control unit (multi-drop connection)
・
RKC standard communication
•
Communication with host computer
・・・・・・・・・・・・・・・・・・・
RKC standard communication
Select the communication speed from the four types of 2400, 4800, 9600 and 19200 bps by the dip
switch in the PCP module (Same for data configuration).
For details on the dip switch settings, see
3.3.4 Settings before operation (P. 31)
.
7
8
9