3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
32
Unit address settings
When each control unit is multi-drop connected to host computer or operation panel, set the address
of each control unit using the unit address setting switch in the PCP module.
Use a very small blade screwdriver to set the unit address on the unit address setting switch located on
the front of each PCP module.
8
7 6
5
4
3
2
1
0
F
E
D
C
B A 9
PCP module
Setting range: 0 to F (hexadecimal)
0 to 15 (address number)
Unit address setting switch
Set the unit address such that it is different to the other addresses on the some line.
Otherwise, problems or malfunction may result.
If multi-drop connected to the host computer, can correspond to sixteen control units
maximum.
If multi-drop connected to the dedicated operation panel, can correspond to sixteen control
units maximum.
If multi-drop connected to the OPM (Z-191 specifications) or OPM-H (Z-191 specifications)
operation panel, can correspond to eight control units maximum. (Unit address setting
switch: 0 to 7.)