7. FUNCTIONS
IMSRM02-E6
83
7.4 Alarms
Alarm (ALM) function sets up the alarm status when the measured value (PV) or the deviation
reaches the alarm set values. In the alarm status, the alarm output is output, and the alarms are used to
drive the equipment danger signals or the safety equipment.
The output specifications are the relay contact output or the open collector output.
(Specify when ordering)
Relay contact output
circuit diagram
Open collector output circuit diagram
OUT
Common
OUT
Common
24 V DC
+
-
Load
(1) Deviation alarm
If the deviation [Measured value (PV) - Set value (SV)] reaches the alarm set value, the alarm status is
set up. Consequently, if the set value (SV) changes, the alarm set value will also change.
z
z
z
z
Deviation high alarm
When the deviation [Measured value (PV) - Set value (SV)] is the alarm set value or more, the alarm
status is set up.
−
When the deviation is on the positive side
−
When the deviation is on the negative side
Measured value (PV)
Set value (SV)
Set value (SV)
Alarm
set value
Time
Deviation
Time
OFF
OFF
ON
OFF
ON
ON
Measured value (PV)
Measured value (PV)
Measured value (PV)
Alarm
set value
Alarm status
Alarm status
Deviation