92
IMSRM02-E6
8. SPECIFICATIONS
8.1 PCP Module
Basic functions
Data supervision:
Operating and system data
Control unit diagnosis:
Function modules configuration check
Self-diagnostic:
Check item:
ROM/RAM check
Watchdog timer
CPU power supply monitoring
If error occurs in self-diagnosis, the hardware will automatically return
the module outputs to the OFF position.
Memory backup:
Lithium battery for RAM backup, approximate ten years life for data
retention.
Power input
Power supply voltage:
100 to 120 V AC (50/60 Hz), 200 to 240 V AC (50/60 Hz) or 24 V DC
Specify when ordering
Power supply voltage range:
100 to 120 V AC:
90 to 132 V AC
200 to 240 V AC:
180 to 264 V AC
24 V DC:
21.6 to 26.4 V DC
Power consumption:
100 to 120 V AC:
40 VA max.
200 to 240 V AC:
50 VA max.
24 V DC:
21 W max., 1 A or less
Surge current:
30 A or less
Power output (For function modules)
Output voltage/current:
5 V DC,
1.7 A max.
12 V DC, 1.0 A max.
Overcurrent protection:
Fold-back limiting method: 5 V