2. SYSTEM CONFIGURATION
IMSRM02-E6
15
Input A
CT input B
Input A: Alarm output
CT input B: Heater break alarm output
•
Assign CT inputs and DO module alarm outputs within the same control unit.
(Because all control inputs and outputs must be closed within the same control unit.)
•
Up to 10 function modules can be mounted. However, if any specific module is mounted together
with these function modules in the control unit, the maximum number of function modules mounted
becomes less than 10.
If any function module is added to the existing modules, note that the total current consumed by all
of the function modules at a power supply voltage of 5 V or 12 V does not exceed the maximum
power supply capacity of the PCP module (for a power supply voltage of 5 V: 1700 mA in total, or
for a power supply voltage of 12 V: 1000 mA in total) by referring to
Consuming current of each
function module
on the next page.
Power supply side
(PCP module)
Power supply consumption side
(Function module: Up to 10 modules)