2. SYSTEM CONFIGURATION
IMSRM02-E6
16
Consuming current of each function module
Function module
Power supply
voltage of 5 V
Power supply
voltage of 12 V
DO relay contact output module
45 mA
140 mA
DO open collector output module
45 mA
0 mA
TIO-D module
150 mA
80 mA
TIO-A, B, C, P module
150 mA
40 mA
DI module
30 mA
0 mA
CT module
110 mA
0 mA
[Example]
Example in which the maximum number of function modules (mainly TIO modules) is mounted at a
power supply voltage of 12 V.
z
z
z
z
When TIO-D modules are mounted together with other function modules
As the TIO-D module consumes an output current of 80 mA/slot and the TIO-B module, an output
current of 40 mA, the following current is obtained.
For TIO-D (3 modules): 80
×
3 =
240 mA
,
For TIO-B (4 modules): 40
×
4 =
160 mA
The above current does not exceed the maximum power supply capacity (1000 mA). However, as one
TIO-D module is assumed to correspond to two function modules,
up to 7 function modules
can be
mounted.
TIO-D
80 mA
TIO-D
80 mA
TIO-D
80 mA
TIO-B
×
4
160 mA