6.2 Module Replacement Procedure
PCP module replacement
To remove the PCP module from the mother block, follow the reverse order of module mounting.
z
z
z
z
Replacement procedure
1.
Turn off the power to the control unit.
2.
Remove the module mainframe from the mother block.
3.
Mount the normal module mainframe.
A snapping sound will be heard when module mainframe is securely connected to mother block.
4.
Turn on the power to the control unit.
5.
Replacement end.
As all data on PID constants, alarm set values, etc. is managed by the PCP module, it is
necessary to re-enter and re-set all data when the PCP module is replaced.
However, re-entry and re-set are not required in the following cases.
•
When data backup software is operating in the module by the external host computer.
•
When it is set on the operation panel so that data on the operation panel side is transferred
to the control unit side when the power is turned on again.
For details, see the
Operation Panel Instruction Manual (OPM: IMSRM03-E
,
OPL-A: IMSRM11-E
, OPM [Z-191 specifications]: IMSRM21-E
, OPM-H
[Z-191 specifications]: IMSRM26-E
)
.