5. WIRING
IMSRM02-E6
63
TIO module wiring saving
As the output terminals for voltage pulse output or 1 to 5 V DC voltage output commonly use the
minus line in the control unit, it is possible to omit the remaining wiring on the minus side by
commonly using a minus terminal on one module.
[Example]
When twelve SSR units are connected to six TIO-B voltage pulse output type modules
: Connecting
terminals
Common
minus wire
SSR
SSR
SSR
SSR
SSR
SSR
SSR
SSR
SSR
SSR
SSR
SSR
−
+
−
+
−
+
−
+
−
+
−
+
−
+
−
+
−
+
−
+
−
+
−
+
Six TIO-B module (Voltage pulse output): Output total, twelve points
For control output types other than voltage pulse output and 1 to 5 V DC voltage output, no
common minus can be connected.
Connect a common minus wire to any of the minus side output terminals on the TIO module
(any of OUT1 or OUT2 is available).