Depending on the option selected for 'Response to EC/pH alarm', the program will
either be paused or irrigation will continue with fresh water.
Check:
the measured EC value (control, monitor or pre-blending EC) and compare this
value with the calculated EC setpoint.
the pre-set EC setpoint.
the 'Minimum EC zone' or the 'Maximum EC zone' are set too low.
the Radiation influence on the EC value.
the influence of the EC value of the supply water.
whether the correct recipe has been selected, and the dosage ratio is set
correctly.
whether the EC sensor is dirty and needs cleaning.
Pre-blending EC too high, group has been paused
The EC value (control, monitor or pre-blending EC) is too high.
Depending on the option selected for 'Response to EC/pH alarm', the program will
either be paused or irrigation will continue with fresh water.
Check:
the measured EC value (control, monitor or pre-blending EC) and compare this
value with the calculated EC setpoint.
the pre-set EC setpoint.
the 'Minimum EC zone' or the 'Maximum EC zone' are set too low.
the Radiation influence on the EC value.
the influence of the EC value of the supply water.
whether the correct recipe has been selected, and the dosage ratio is set
correctly.
whether the EC sensor is dirty and needs cleaning.
Control EC sensor alarm, group has been paused
The value measured by the sensor is outside the measurement range.
Check the sensor.
Contact your installer.
Monitor EC/pre-measurement sensor alarm, group paused
The value measured by the sensor is outside the measurement range.
Check the sensor.
Contact your installer.
External EC control alarm, group has been paused
External EC control has triggered an alarm. As a result, EC control has stopped and
the valve group in question has been paused.
The valve group will only resume after you initiate a manual start. The fogging
program will, however, continue.
Check EC control.