Alarms and notifications
If an alarm is triggered, the controller will pause, stop or continue irrigation. This
depends on the alarm message that has been triggered. The most recent alarm
message will remain on the display. Write down the alarm message if you need to
contact your installer. Also see: "Alarm messages" on page 69, Remedying faults and
errors.
Notifications provide information on the status of the valve group and the valve that
are currently active. All notifications appear on the display, but are automatically
removed after a certain amount of time. If a printer is connected, notifications can
also be printed. Please note that notifications are not saved.
Press the Delete (D) button to remove an alarm message or notification.
5.1
Flow
Flow rate too low, valve skipped
The valve has been skipped, because the measured flow rate is too low.
The controller will continue with the remaining valves in the valve group.
Check:
Is the 'Minimum flow rate' set too high?
Flow rate too low, valve paused
The valve group has been paused, because the measured flow rate is too low. The
fogging program will continue.
Check:
Is the 'Minimum flow rate' set too high?
The valve group will only resume after you initiate a manual start.
Flow rate too high, valve skipped
The valve has been skipped, because the measured flow rate is too high. The
controller will continue with the remaining valves in the valve group.
Check:
Check whether the 'Maximum flow rate’ is set too low.
Flow rate too high, valve paused
The valve group has been paused, because the measured flow rate is too high. The
fogging program will continue.
Check:
Check whether the 'Maximum flow rate’ is set too low.
The valve group will only resume after you initiate a manual start.