Ignore main pause time
No: The valve group will only be activated once the main pause time has elapsed.
Yes: The valve group will be activated immediately, even if the main pause time has
not yet elapsed.
If the valve group is already active, the start signal will not be stored.
If another valve group is already active, the start signal will be queued.
3.3.1.12
Weather influences
To enable weather influence control, enter the following settings:
Set 'Wind speed measurement' (in system definition) to 'Yes'.
Set 'Rainfall detection' to 'Yes'.
Start of wind trajectory
End of wind trajectory
Wind influence on time
Wind influence on volume
Maximum wind speed for start
Start if raining
Path: Settings>Programs>Program name>Weather influence
Start of wind trajectory 0 - 40 m/s
The wind speed at which the wind influence will start.
End of wind trajectory 0 - 40 m/s
The wind speed at which the wind influence will be at its maximum.
Wind influence on time
The maximum duration by which an irrigation cycle may be extended. This maximum
influence will be applied when the value set for 'End of wind trajectory' is reached.
Wind influence on volume 0 - 99999 Litres
The maximum number of litres that an irrigation cycle may be increased by. This
maximum influence will be applied when the value set for 'End of wind trajectory' is
reached.
Maximum wind speed for start 0 - 40 m/s
The wind speed below which a new start may still be executed.
Start if raining
No: No new start will be executed if rain is detected.
Yes: A new start may be executed if rain is detected.
Aqua CX300
42