Response to EC pre-blending alarm
The action that you want the controller to take when an EC or pH alarm is triggered:
Pause: Pause irrigation
Continue: Continue irrigation with fresh water (without drain water).
Gain of EC pre-blending 0 - 1000
The factor that determines how many seconds the mixer valve must be actuated, if a
difference arises between the calculated EC setpoint and the measured EC.
EC pre-blending differential time 0 - 1000 sec.
0: The differentiation time is disabled. This mode will suffice in nearly all cases.
1 -> 300: In the case of a mixer valve: The degree to which the control pulse of the
mixer valve will be attenuated.
Maximum control percentage of EC pre-blending 0 - 100 %
1 -> 99: The percentage of the total run time that the mixer valve will be actuated.
100: Maximum control percentage EC has no influence.
3.3.1.4
pH control
Enable pH control
pH setpoint
Minimum alarm zone of control pH
Maximum alarm zone of control pH
Maximum difference of monitor pH
Minimum fresh water pH
Maximum fresh water pH
Alarm delay of control pH
Alarm delay of monitor pH
Alarm delay of fresh water pH
Moving average active
Time span of moving average
Gain
Differentiation time
Maximum control percentage
Integration time
Path: Settings>Programs>Program name>pH control
Enable pH control
No: Not active.
Yes: Active.
pH setpoint 0 - 9.9.
The pH value that the controller will aim to reach. This pH setpoint applies to all
valves of the relevant valve group.
Aqua CX300
29