End of radiation trajectory for EC 0 - 1000 W/m²
The radiation level at which the radiation influence on the control EC is at its
maximum.
Max. radiation influence on EC -9.9 - 9.9 mS/cm
The maximum value by which the EC may be lowered (or raised) based on the
radiation level.
Ratio of dosage valve 1 0 - 500
In the case of control using dosage valves: The dosing ratio of the EC valve in relation
to the other EC valves. In setting the dosing ratios, it is the relationship between the
values that is important, rather than the specific value of each valve.
The same applies to the other dosage valves.
Moving EC average active
Enables you to activate the calculation of a moving average of the EC measurements.
Time span of moving EC average
The time span over which a moving average of the EC measurements will be
calculated.
Pre-measurement
No: Not active.
Yes: Active. The pre-set EC setpoint will be added to the pre-measurement EC.
EXAMPLE:
The measured EC = 1mS
The pre-set EC setpoint = 2mS
The calculated EC setpoint = 1 + 2 = 3 mS
3.3.1.2.1 EC control with mixer valve
EC gain 0 - 1000
The factor that determines how many seconds the dosage valves must be actuated,
when a difference arises between the calculated EC setpoint and the measured control
EC.
EC differentiation time 0 - 1000 sec.
0: The differentiation time is disabled. This mode will suffice in nearly all cases.
1 -> 300: In the case of a mixer valve: The degree to which control of the mixer valve
will be damped.
Aqua CX300
25