48
GENERAL
Winter Set user limitations
NAME
Description
Value
low
Lower winter limit
12°C
Up
Upper winter limit
30°C
Summer Set user limitations
NAME
Description
Value
low
Lower summer limit
14°C - 40% RH
Up
Upper summer limit
30°C - 75% RH
Timer
NAME
Description
Value
Back to Main
Back to main menu
5 min
Switch-off Display
Switch off display
5 min
Enable Dehumidifier Alarms
NAME
Description
Value
01:
Dehumidifier 1 alarm
no
02:
Dehumidifier 2 alarm
no
Enable pump anti-seize
NAME
Description
Value
Enable
Enable function
no
Days of inactivity
Days of inactivity
7 days
Operation
Minutes of operation
5 min
FLOOR COMPENSATION LINE SETTINGS
WINTER parameters
NAME
Min
Max
Name
Value
T.Ext
-5°C
20°C
Off set
0
T.Del
45°C
22°C
SUMMER parameters
NAME
Min
Max
Name
Value
T.Ext
23°C
32°C
Off set
0
T.Del
20°C
15°C
Dynamic compensation
NAME
Type
Value
Enable
Enable function
No
KDSum
Summer multiplier coefficient
3
Tmin
Minimum summer temperature
10°C
KDWin
Winter multiplier coefficient
3
Tmax
Maximum winter temperature
50°C
MIXING VALVE parameters
NAME
Type
Value
PB
Proportional band
5.0°C
IT
Integral time
30 seconds
DB
Dead band
0.4°C
K
Approach sensitivity
5
STRUCTURAL/ATTENUATION parameters
NAME
Type
Value
Delta
Delta structure
4.0°C
Win Attenuation
WINTER attenuation
2.0°C
Sum Attenuation
SUMMER attenuation
2.0°C