16
SE
TTINGS \ GENER
AL
MASTER - SLAVE S1 SETTINGS
Set the S1 Series parameters, in MASTER-SLAVE mode
S1
MASTER
SLAVE
PARAMETERS
These parameters allow setting the control unit for .NET configuration.
The architecture must, therefore, provide for the presence of a MASTER connected to
the S1 serial bus. You can set the following parameters:
TimeOut: maximum time with absence of communication between the MASTER and
the control unit.
Config Slave:
• No: In this case, the control unit is independent and manages all the components
of the system.
• Master: In this case the controller is connected with .NET system including 1 Master
controller.
• Master_PC: In this case the controller is connected with .NET system including a PC
as system supervisor and 1 Master controller.
Clock Master: if the control unit is configured as SLAVE configuring:
• YES: The control units draws time-related information from the MASTER.
• No: The control unit is independent with its clock on board.
MASTER -SLAVE S1
──────────────────────
TimeOut: 03m 000m
Config.Slave:No
Clock Master:No
──────────────────────
Parameters
.net configuration
ANALOG IN Wi-M1 / Sx
Type of Temperature, Humidity, Air Quality sensors
It shows the electrical type of Temperature, Humidity, Air Quality sensors, which must
be connected to the WI-M1/Sx unit.
Temp: The values of the temperature sensor are: NTC (default), 0/1V, 0- 10V, 4/20mA,0/5V.
Humidity: The values of the humidity sensor are: NTC, 0/1V, 0-10V, 4/20mA (default),0/5V.
CO2: The values of the air quality sensor are: NTC, 0/1V, 4/20mA (default),0/5V.
Analog In
<WI-M1/S1/S2/S3>
──────────────────────
Temp: NTC
Humidity: 4/20mA
CO2: 4/20mA
──────────────────────
Type of sensors
ANALOG IN Wi-Z / Wi-U
Type of Temperature, Humidity, Air Quality sensors
It shows the electrical type of Temperature, Humidity, Air Quality sensors, which must
be connected to the WI-Z / WI-U unit.
Temp: The values of the temperature sensor are: NTC (default), 0/1V, 0- 10V, 4/20mA,0/5V.
Humidity: The values of the humidity sensor are: NTC, 0/1V, 0-10V, 4/20mA (default),0/5V.
CO2: The values of the air quality sensor are: NTC, 0/1V, 4/20mA (default),0/5V.
Analog In
<WI-Z / WI-U>
──────────────────────
Temp: NTC
Humidity: 4/20mA
CO2: 4/20mA
──────────────────────
Type of sensors Wi-Z
PASSWORD
Set additional passwords
to access the user and technical setting menus.
Password
──────────────────────
User: 0123
Technical: 9876
──────────────────────
Values to access
menus
SELECT LANGUAGE
Select on-screen display language
Allows selecting the language in which the information is displayed on screen. ( ITALIAN
- ENGLISH - SPANISH )
Summer Time: makes it possible to disable the summer time
(YES/NO)
SELECT LANGUAGE
──────────────────────
Change lang. UP
ENGLISH (UK)
Summer Time: No