(3): SYSTEM PARAMETER
CONFIGURATION
Once type of system has been defined, you can now modify its
operating parameters. In succession, you can set:
Winter compensation line
Summer compensation line
Delta structure coefficient
Mixing parameters
Dynamic compensation
WINTER
COMPENSATION
LINE
The parameters to be entered in the screen represent the
characterisation of the compensation curve shown in the
figure below. The control unit, will adjust the water delivery
temperature according to the outdoor temperature.
Heating Curve (winter compensation).
During the calculation phase, in winter operating mode, the control unit, given the measured outdoor temperature, will calculate
a temperature that we will indicate as T
MCL
, i.e., a temperature calculated through the compensation line.
Winter Compensation Line Reference Settings
WALL/CEILING
Name
Min
Max
Name
Val
TExt
-5°C
10°C
Off.
0
Del.T
48°C
36°C
FLOOR
Name
Min
Max
Name
Val
TExt
-5°C
20°C
Off.
0
Del.T
45°C
22°C
10°C
Max External T. °C
-5°C
Min External T. °C
36°C
Min Del. T. °C
48°C
Max Del. T. °C
T
MCL
Offset °C
“Parallel shifting”
Delivery Temp. °C
External
Temp. °C
T
MCL
= Temperature calculated through the compensation line
SYS[1] WinComp 01
──────────────────────
Min Max Off
TExt:-05.0 20.0 0.0
TDel: 45.0 22.0
──────────────────────
Winter compensation
curve
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ S
YSTEM
\ S
ETTINGS
\
W
INTER
COMPENSATION