DEHUMIDIFIER / INTEGR
ATION
SETTINGS / ZONES / DEHUMIDIFIER / INTEGRATION
ENABLE AHU INTEGRATION
Change the integration features for AHU/UxBUS:
En.Inv: (Yes / No) ON / OFF for winter integration
Diff. : Differential value for winter switch-on
En.Sum: (Yes / No) ON / OFF for summer integration
Diff. : Differential for summer switch-off
Pump: The pump for integration is activated:
- both in summer and in winter - in summer only - in winter only
Duct Tmp: The temperature detected in the ducts is shown.
AHU[1]
›››
AHU[8]
AHU[1] ntegrat.
──────────────────────
En.Win:No Diff.:03.0°C
En.Sum:No Diff.:03.0°C
──────────────────────
Pump:Summer
Duct Tmp:00.0
SETTINGS / ZONES / DEHUMIDIFIER / INTEGRATION / SET MIX
AHU INTEGRATION PARAMETERES
Set the parameters for integration:
(Clicking on PRG key the screenshot “Enable AHU Integration“ shows the
following parameters)
PB: Proportional band.
K: Adjustment coefficient.
TI: Integral time.
DB: Dead band.
Win: Reference winter temperature.
Sum: Reference summer temperature.
AHU[1] Set Mix
──────────────────────
PB:05.0°c K: 04
TI:030S Win Sum
DB:0.4°C 22.0 25.0
──────────────────────
ZONES/ OFFSE
T
SETTINGS / ZONES / OFFSET
ROOM SENSOR CALIBRATION
Modify the room sensor calibration
The temperature and humidity measurement correction values of the selected sensor
are set.
Offset 01
──────────────────────
Tmp Hum
ZONE 1 0.0 0
──────────────────────
Value calibration
Room Sensor
SYNOPTIC
SYNOPTIC SETTINGS
CHANGE SETTINGS:
SYNOPTIC MENU
SYNOPTIC
Mixing valves *
Main Relays *
Exp Zone Relay *
Exp AHU Relay *
TC Terminals *
MIXERS
SYNOPTIC / MIXERS
MIXERS SYNOPTIC
C
HANGE
THE
MIXING
VALVE
SYNOPTIC
MENU
SETTINGS
SYS[1]
›››
SYS[8]
SYST[1] MIX An 01
Output 00.0