30
The control system consists of the WI-M1 WI-S2 WI-S3 WI-S4 boards, the WI-Zxx WI-Ux expansion
units and the UI/PRO user interface, which communicates via a data BUS on a 6-pin RJ12 cable.
To ensure proper system operation, the specific unit addresses must be set in order to identify
them univocally.
Therefore, proceed with the unit address configuration.
UI/E
GRAPHICS
TERMINAL
ADDRESS
CONFIGURATION
Proceed as follows:
1) power the unit;
2) prepare a UI/PRO terminal and connect it to the central unit by means of an RJ12 cable;
3) to enter configuration mode, press
Up
Enter
Down simultaneously for at least 5 seconds;
4) once this operation has been carried out, screen 4 will appear on the terminal);
5 )to modify the terminal address, press
Enter. The cursor will place itself in the address field (nn);
6) use buttons
Up
Down to select the required address;
7) confirm the address by pressing
Enter. Mask 8) will appear.
The possible address values that can be allocated to the UI/PRO graphics terminal range between 0-32 (available addresses to
identify the network drives). If the value 0 is set, the terminal communicates only with the board connected directly to it and the
I/O Board address field will disappear.
NB: Address
10
is allocated to the terminal in its standard operation.
NB: Address
0
is allocated to the terminal when the latter must be used to configure the addresses of the WI-xx boards (see WI-M1/S2/
S3/S4 address setting).
To switch from one unit to other one change the field I/O Board address: 02 = Wi-S2 , 03 = Wi-S3
Display address
setting..........: nn
I/O Board address: xx
1
4
3
2
Bus RJ12
6 pole
5 sec
5
6
7
8
nn
: xx
ON
Display address
setting..........: nn
I/O Board address: xx