26
CONFIGURE EXP U
SETTINGS / ZONES / DEHUMIDIFIER / CONFIGURE EXP U / BLK VENT-RINN
VENTILATION / RENEWAL BLOCK
Change the operation ventilation/renewal:
Enable: Yes/No. If the function is enabled, on reaching the Set+ Diff/2 the pump
operation is blocked, exceeding the Set + Diff the ventilation/renewal feature is also
blocked.
Winter Diff.: temperature difference according to which the ventilation / renewal in
winter is blocked.
Summer Diff.: temperature difference according to which the ventilation / renewal in
summer is blocked.
Channel Air Tmp: it displays the inlet temperature if the duct sensor is installed.
AHU[1]
›››
AHU[8]
AHU[1] Block /
──────────────────────
Enable:Yes
Diff. Win: 2.0°C
Diff. Sum: 2.0°C
──────────────────────
Channel Air Tmp:
WINTER
function (*)
fan
deum pump
fans + dampers
forced renewal
Room
Temp
<=
Set + Diff
Room
Temp
>
Set + Diff
Room
Temp
<=
Set+ Diff/2
Room
Temp
>
Set + Diff/2
Room
Temp
<=
Set + Diff
Room
Temp
>
Set + Diff
& <
Room Set
ON
ON
ON
ON
OFF
Restarting on
reaching the
set values
OFF
ON
Turning off on
reaching the
set values
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SUMMER
function (*)
fan
deum pump
Room
Temp
>=
Set + Diff
Room
Temp
<
Set - Diff
Room
Temp
>=
Set - Diff/2
Room
Temp
<
Set - Diff/2
ON
ON
ON
ON
OFF
Restarting on
reaching the
set values
OFF
OFF
OFF
OFF
OFF
(*) = Status of the ventilation/ renewal feature within the time range.
CONFIGURE EXP U
SETTINGS / ZONES / DEHUMIDIFIER / CONFIGURE EXP U / HUMIDIFICATION
ENABLE AHU PUMP IN HUMIDIFICATION MODE
Yes / No: Enable/Disable the AHU pump in case of humidification input (winter season).
AHU[1]
──────────────────────
Enable pump
humidification:
Yes
──────────────────────