Set the activation time
for production (PROD: Chiller, Boiler,Heat Pump) and for
the activation and switch-off of the system PUMP.
S
TART
-
UP
AND
SWITCH
-
OFF
PARAMETERS
You can set the following parameters:
PROD:
Start-up: Seconds of delay upon start-up after production request.
PUMP:
Start-up: Seconds of delay upon start-up after production request.
Switch-off: Seconds of forced activation following the suspension of the production
request.
Start-Up/Switch-off
──────────────────────
Start Stop
PROD: 010s
PUMP: 045s 180s
──────────────────────
Delay Times
ANTIFREEZE
Set activation temperature
for the ANTIFREEZE function and the operating
hysteresis.
Tmp: Minimum room temperature to activate zone input and energy generation.
Hys.: Minimum hysteresis minima to swith off the operation.
EA: enables/disables the defrost operation according to the outdoor temperature (it
activates the energy generation).
EM: enables/disables the defrost operation also for the system pump and for the mixing
valves.
T.Set A: selects the activation temperature for the defrosting mode according to the
outside temperature.
Tmr Ctrl: time duration between two consecutive temperature control operations for
the defrosting function.
Tmr ON: activation time for the generation controls and optionally for the pumps as well
as the mixing valves to carry out the defrosting function. (between 1 and 15 minutes)
ANTIFREEZE
Env. │Temperature Ext.
Tmp.: │EA:No EM:No
05.0c│T.Set A: 05.0°c
Hys.:│Tmr Ctrl:02 hou
1.0°c│Tmr On: 10 min
─────┴────────────────
Par. Start/stop log.
THERMAL
Vary the parameters of the “Thermal” function
Enable: enables the THERMAL function.
Tmp: Thermal function activation temperature.
Hyst: Start-up switch function hysteresis.
Tstart: System pump activation time.
Tstop : Delay between cycles.
Cycles: Number of cycles that can be activated before the alarm locks the function.
THERMAL
──────────────────────
Enable:No Tmp:45.0
TStart:015s Hyst:2.0
TStop: 090s Cycles:05
──────────────────────
Parameters
Start/stop logics
ENABLE ALARMS
Enable the buzzer in the event of alarms
A
LARM
ENABLING
PARAMETERS
Alarm buzzer enabling
No: the buzzer does not set off
Yes: The buzzer sets off in the event of an alarm
ENABLE ALARMS
──────────────────────
Buzzer: No
──────────────────────
Buzzer in the
event of alarms
HIGH HUMIDITY ALARM
Enable the high humidity alarm
If the alarm is enabled, all sensors (which exceed the dewpoint set value during SUMMER
for a period longer than the specified minutes of delay) are turned OFF while signalising
the humidity alarm.
P
ARAMETERS
HIGH
HUMIDITY
ALARM
Enable: Enabling the alarm (YES/NO).
BlkD: Enabling the dehumidifier shutdown in case of active alarm (YES/NO).
Set: besides the threshold which triggers the alarm.
Delay: Minimum time to wait before signalising the alarm and turning off the zone.
HIGH HUMIDITY AL.
──────────────────────
Enable:No BlkD:No
Set:A.A °C
Delay:05 min.
──────────────────────
Parameters