WINTER COMPENSATION
Modify the winter compensation line:
TExt –Min: Minimum External Temperature
TDel –Min: Minimum Delivery Temperature
TExt –Max: Maximum External Temperature
TDel –Max: Maximum Delivery Temperature
Off: Offset (parallel shifting of the compensation line).
SYS[1] WinComp 01
──────────────────────
Min Max Off
TExt:-05.0 20.0 0.0
TDel:45.0 22.0
──────────────────────
Winter compensation
curve
SUMMER COMPENSATION
Modify the summer compensation line:
TExt –Min: Minimum External Temperature
TDel –Min: Minimum Delivery Temperature
TExt –Max: Maximum External Temperature
TDel –Max: Maximum Delivery Temperature
Off: Offset (parallel shifting of the compensation line).
SYS[1] SumComp 01
──────────────────────
Min Max Off
TExt:23.0 32.0 0.0
TDel:20.0 15.0
──────────────────────
Summer compensation
curve
ADJUSTMENT
Mitigation:
Value to be subtracted from (winter) or added to (summer) the set value ( temperatura
and humidity), when the zone is running in economony mode.
SYS[1]Adjustment 01
──────────────────────
<<Pgm/Man>> tmp Hum
Summer: 2.0 10
Winter: -2.0 -10
──────────────────────
Eco. adjustment
Manual program
DELTA STRUCTURE
Modify the system parameters:
Delta Structure: [0-9.9°C] surface structural coefficient.
This coefficient makes it possible to consider the thermal inertia of the structure on
which the system is placed. This parameter affects the supply water temperature.
SYS[1] DELTA STR.01
──────────────────────
Delta Structure: 2.0
──────────────────────
Type of screed
SE
TTINGS / SY
STEM / SE
TTINGS
MIXING PARAMETERS
Modify the mixing parameters: (See delivery temperature control)
PB: [2-10 °C]Proportional band.
IT: [0-500 sec] Integral Time.
DB: [0-2°C] Dead band.
K: [0-10] Approach speed coefficient.
SYS[1] Set Mix 01
──────────────────────
PB:05.0°C
IT:030s K: 04
DB:0.4°C
──────────────────────
Mixing valve
settings
DYNAMIC COMPENSATION
Modifiy the dynamic compensation parameters
Enable: Yes/No. Enable dynamic compensation
Pilot No.: Pilote zone identification number, which affects the delivery temperature
value obtained through the compensation line.
KDSum: [0-9] Summer multiplier coefficient.
KDWin: [0-9] Winter multiplier coefficient.
SYS[1] DynComp 01
──────────────────────
Enable:Yes Pilot:01
KDSum:3 KDWin:03
──────────────────────
Room dynamic
compensation
SUPPLY TEMPERATURE LIMITS
Supply water temperature limits of the system
TMin: [5-15°C] Limit temperature for calculating the summer value.
TMax: [30-70°C] Limit temperature for calculating the winter value.
Supply temp. limits
──────────────────────
SUMMER WINTER
TMin:10.0 TMax:50.0
──────────────────────
Room dynamic
compensation