6) SYSTEM ALARM — EXTERNAL SENSOR:
──────────────────────
EXTERNAL TEMPERATURE
This error occurs when the control unit does not detect the external temperature signal. NB: all
the systems continue to operate, considering, during winter mode, the external temperature
value set to +5°C and the maximum set to +30°C.
7) SYSTEM ALARM — DELIVERY SENSOR:
ALARM
DELIVERY SENSOR
──────────────────────
Enter Display
DELIVERY TEMPERATURE
──────────────────────
SYSTEM:SYST[1]
This error occurs when the control unit does not detect
the delivery temperature signal.
NB: system Syst[1] is deactivated.
8) ROOM ANTIFREEZE:
ROOM
ANTIFREEZE
Enter Display
ANTIFREEZE
──────────────────────
SYSTEM:SYST[1]
This error occurs when, during winter, the temperature
of a zone drops below 5°C (settable). All the zones are
activated. The alarm is reset when the temperature in all
the zones exceeds 6°C (settable).
9) THERMAL ALARM:
THERMAL
ALARM
Enter Display
THERMAL
──────────────────────
SYSTEM:SYST[1]
This occurs when, during winter, the delivery sensor
detects a temperature of 45°C (settable) for a certain
amount of time while the system is off.
10) WI-Z UNIT ALARM:
OFF-LINE
Wi-Z
──────────────────────
Enter Display
Exp OffLine Wi- 1
──────────────────────
Wi-Z11: Wi-Z12:
Wi-Z13: Wi-Z14:
Wi-Z15: Wi-Z16:
Wi-Z17: Wi-Z18:
In the event of failed communication, a bell will appear
next to the expansion.
11) MIX DAMAGE ALARM:
MIX
DAMAGE
──────────────────────
Enter Display
Mix Damage
──────────────────────
Mix 1: Mix 2:
Mix 3: Mix 4:
Mix 5: Mix 6:
Mix 7: Mix 8:
Reset man:
In case of alarm the symbol of a bell appears next to the
damaged mixer.
The control Reset man. makes it possible to reset the
alarm manually.
12) WI-U UNIT ALARM:
OFF-LINE
Wi-U
──────────────────────
Wi-U11: Wi-U12:
Wi-U21:- Wi-U22:-
Wi-U31:- Wi-U32:-
Wi-U41:- Wi-U42:-
In the event of failed communication, a bell will appear next to the expansion.
13) MAIN UNIT ALARM:
OFF-LINE
Main unit
──────────────────────
Wi-M1: -Yes Wi-S2: Yes
Wi-M1: Yes Wi-S2: Yes
In the event of failed communication, a bell will appear next to the control unit (provided
that it is configured)
YES = Main unit OFFLINE
-
YES = Main unit ONLINE
-
NO = Main unit not configured