47
A
LARMS
AND
D
AT
A
T
ABLES
D
EFAULT
VALUES
TYPE OF SYSTEM
NAME
TYPE
Structure
Type of heating
Wall/Ceiling
Mix type
Type of mixing valve
An
Volt
Min - Max Voltage
0 - 10 V
B!KLIMAX COMPENSATION LINE SETTINGS
WINTER parameters
NAME
Min
Max
Name
Value
T.Ext
-5°C
10°C
Off set
0
T.Del
48°C
36°C
SUMMER parameters
NAME
Min
Max
Name
Value
T.Ext
20°C
30°C
Off set
0
T.Del
16°C
12°C
STRUCTURAL/ATTENUATION parameters
NAME
Type
Value
Delta
Delta structure
2.0°C
Win Attenuation
WINTER Attenuation
2.0°C
Sum Attenuation
SUMMER attenuation
2.0°C
CLIMATE
NAME
CLIMATE
SEASON
Type
Ex room
Summer/Winter
DATA TABLES
18) ERRORS-FAILURES UxBUS:
Block Alarm
UxBUS
Enter to view
Errors/Faults UC- 0
──────────────────────
Supply sensor:-
Evaporation sensor:-
Undercool. sensor:-
Overheating sensor:-
──────────────────────
Pres. next Alm
Supply sensor: Failure of the flow sensor (NTC1 sensor).
Evaporation sensor: Failure of the evaporator sensor
(NTC2 sensor).
Undercool. sensor: Failure of the subcooling sensor C2
(NTC6 sensor).
Overheating sensor: Failure of the overheating sensor
(NTC4 sensor).
Errors/Faults UC-0
──────────────────────
Undercooling sens.:-
Water temp. sensor:-
Compr.temp.sensor :-
Outdoor.temp.sens.:-
──────────────────────
Pres. next Alm
Undercooling sens. Failure of the subcooling sensor C1
(NTC5 sensor).
Water temp. sensor: Failure of the water temperature
sensor (NTC7 sensor).
Compr. temp. sensor: Failure of the compressor
temperature sensor (NTC3 sensor).
Outdoor. temp. sens.: Failure of the external temperature
sensor (NTC8 sensor).
Errors/Faults UC-0
──────────────────────
Pressure transduc.:-
Press. transduc.A:-
Press. transduc.B:-
──────────────────────
Pres. next Alm
Pressure transduc.: Failure of cooling transducer
pressure.(*)
(*) Capacitor probe (in case of UAP 200)
Press. transduc.A: Failure of differential pressure sensor
in the renewal area.
Press. transduc.B: Failure of differential pressure sensor
in the expulsion area.
19) FAILURE AQ SENSOR ALARM:
QA out of order
──────────────────────
QA-1:- QA-5:-
QA-2:- QA-6:-
QA-3:- QA-7:-
QA-4:- QA-8:-
In this screen through the display of the alarm, you can see if the (configured) AQ sensor,
not noticing a correct value, shows an error.
= Error
-
= Configured sensor is running or the sensor is not configured