(6): GENERAL
CONFIGURATIONS
Once the system - zones - dehumidifiers have been defined, you can proceed with the general configurations.
T
HERMAL
PARAMETERS
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ G
ENERAL
\
T
HERMAL
The "thermal" function activates an automatic heat dissipation
algorithm. This logic is available only in Winter operating mode
and is activated only when there is no system low temperature
request.
You can set the following parameters:
Enable: Yes/No Enable/Disable function.
Tmp: Function activation system delivery temperature.
Hyst: Operating hysteresis.
Tstart:Pump operation time.
Tstop:Delay between dissipation cycles.
Cycles: Number of dissipation cycles before the alarm locks
the function.
Below are listed the default values and the pump activation
scheme according to the delivery temperature.
THERMAL
──────────────────────
Enable:No Tmp:45.0
TStart:015s Hyst:2.0
TStop: 090s Cycles:05
──────────────────────
Parameters
Start/stop logics
THERMAL OPERATING LOGIC:
The starting condition is that the system must be on standby
(no production request, recirculating mixing valves, pump off).
If, for any reason, the delivery temperature rises above 45+2°C,
then the thermal function will be activated. This will simply
activate the system pump (15 sec) and the zone output. If this
operation does not bring the temperature back to 45-2°C, the
function will be reactivated after a 90 sec delay for the number
of dissipation cycles (5 cycles). At the end of all the cycles, if the
temperature has not decreased, the thermal alarm will set off.
Name
Description
Default
value
Enable
Enable function
Yes
Tmp
Activation temperature
45°C
Hyst
Operating hysteresis
2.0°C
TStart
Pump activation time
15 s
TStop
Delay
90 s
Cycles
Number of cycles
5
Activation
Temperature 45 °C
System
delivery
temperature
+2°C
-2°C
System
Pump
On
Off