Change the shifting mode in the menus:
mode: Standard/Easy, in the “Easy” mode, from the main screen shot, clicking on “start”,
the screenshot of the SETTING for zone temperature and humidity is visible.
Shifting mode
mode:Simplified
──────────────────────
Modality Surfing
to menus
DEHUMIDIFICATION / INTEGRATION DELAY ACTIVATION
Set the delay time at the start of dehumidification or integration
command.
NB: This delay is useful in combination with the heat pump input in sanitary mode in
order to avoid alarms in the dehumidifiers due to high inlet water temperature.
Delay Deum. e Int.
----------------------
Dly act.: II min
──────────────────────
Delay activation
dehum. e integrat.
LOCKING THE LOW TEMPERATURE DEHUMIDIFICATION
Locking the dehumidification mode:
The dehumidification mode is locked if there are low temperature values and high
humidity values. In this way too cold air is prevented from coming into the room. This
is controlled through a threshold value based on DP (dew point).
The function is enabled by EN_CTRL parameter.
Block Dehum. LT
──────────────────────
EN_CTRL: B
LIV_CTRL:AA.A °C
──────────────────────
Block activation
dehum. Low Temp.
LOCKING THE ECONOMY SWITCH
Select the temperature value to be used in the Economy operation
mode.
On this window you can select the temperature value to be used in the PGM MAN
operation in the Economy mode.
Two options are available, that is: ATT.COM. and ECO.
ATT.COM. uses the comfort temperature value minus the attenuation value (usually
+/-2 °C).
ECO uses the temperature value set in the time schedule in the economy mode.
SEL TMP ECO PGM MAN
──────────────────────
SEL_ECO: B
──────────────────────
Selector economy
Mode PGM MAN
NO OXIDATION
Set and enable the anti-oxidation function for electro-thermal heads.
On this window you can enable the function by using the parameter En_anti_ox, while
the parameter Day_PGM makes it possible to set the number of waiting days before the
activation of the cycle. The parameter T_On_O_test establishes the duration of this cycle.
No Oxidation
──────────────────────
En_No_Ox: B
Day_PGM: II
T_On_Off_Heads:II min
──────────────────────
Anti oxidation
Heads
MIX DAMAGE
Set and enable the function linked to a damaged mixing valve.
In case of malfunctioning in summer running, this function prevents the over-cooling
of the zones. This operation can be enabled through the parameter En_mix_dan, while
the parameter Delta_tmp makes it possible to set the temperature differential value
to start the cycle. The parameter Delay_on establishes the time delay from the alarm.
Mix Damage
──────────────────────
En_Mix_Dan: Disable
Delta_tmp: 10 °C
Delay_on: 01 min
──────────────────────
Mix Damage
LOAD DEFAULT
Set the control unit with default values and delete the current
configuration.
NB: Upon completing the operation, you must proceed with the control unit
configuration.
Load Default
──────────────────────
No