43
C
ONFIGUR
ATION
A
UTOMATIC
S
EASON
P
ARAMETERS
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ G
ENERAL
\
A
UTOMATIC
S
EASON
Automatic Season
──────────────────────
Auto
Set change:22.0 °C
Sampling:030 sec
Neutral Temp.:1.0 °C
──────────────────────
Change mode
Managing the season in manual/automatic mode.
WINTER
SUMMER
Intermediate
Season
Neutral-T
20 °C
Delivery with external WINTER
compensation logic
Delivery with external Dew
Point compensation logic
T.Ext
P.R.
AUTOMATIC SEASON LOGIC
Outdoor conditions
Every zone has two sets of temperatures, one for each season. According to the outdoor weather conditions, the control unit
will automatically change the season.
Indoor conditions
Given a set range equal to Change Set ± Neutral Temp. , if there is an active zone where the measured temperature is higher
or lower, for a set sampling time and in all the other active zones the measured temperature falls within the set range, then the
reference season will be determined by the zone.
WARNING: This function is activated only for systems that can be hydraulically set to the automatic heating/cooling
mode.
P
RODUCTION
T
YPE
S
ETTING
Set the parameters of the production type
Type: Chiller / Heat pump, it represents the energy
source feeding the system
En Switch Prod: (only with type = Heat pump) Yes/No, if
“Yes” is set in the system, there is another heat generator
(es. boiler) apart from the heat pump.
t. Switch: (default 30 sec) Delay time before changing
primary resource into secondary resource.
Tmp Ext: (default 5°C) set value for outside temperature
below which the controller switches the energy production
from the primary source (Heat pump) to the secondary one
(boiler).
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ G
ENERAL
\
P
RODUCTION
T
YPE
PRODUCTION TYPE
──────────────────────
Type: Chiller
En Switch Prod:No
t.Switch:030 sec
Tmp Ext:05.0
──────────────────────
Production type