Upon completing the deletion, the system restarts and the main screen appears.
We can now proceed with the configuration of the system: After entering the password, then technical menu Step (0), access the
screen for entering the type of system.
STEP A: define the type of system.
The possible settings are the following:
Structure: Type of system structure:
Absent: Non-configured system.
Floor: Floor Structure.
Wall/Ceil.: Wall/Ceiling Structure.
HT + Mix: High tempe mixing valve.
HT: High-temperature.
HTdir: Direct High-temperature.
Mix Type: Type of mixing valve:
An: Analog Mixing Valve:
Min: [0/10V] Voltage to supply the maximum power to the system.
Max: [0/10V] Voltage to supply the maximum power to the system.
Mix DirRev: 0-10V output, direct or reverse to the min/max setpoint for summer mode (Sum) or winter mode (Win)
TDir: 0-10V output following the set min/max direction.
TRev: 0-10V output in the reverse direction to the set min/max one.
NB: During this phase, you can define up to 8 mixing systems.
S
TEP
(2): SYSTEM
CONFIGURATION
The possible settings are the following:
Climate with external sensor
Only the external sensor is installed in this type of configuration.
Delivery temperatures calculated according to the external
compensation curve. The system activates the boiler/chiller and
the pump, adjusting the mixing valve to the required calculated
temperature. Partial disconnection of the system is controlled
by external controls by means of remote thermostats.
Season:
• Winter: Temperature control is activated only during the
winter season.
• Summer Temperature control is activated during
Summer.
• Summer: Temperature control is activated only during the
summer season.
NB: Summer configuration requires extra caution on
system external humidity control
Climate with Ex Room sensor
This type of configuration requires the installation of an external
sensor and of at least one HT/H or HT room sensor.
Season:
• Winter: Temperature control is activated only during
the winter season. The control unit will deactivate all the
summer functions, change of season (will no longer be
enabled), dehumidifier control, etc. Compensation occurs
considering the external temperature curve and (optional)
room dynamic compensation.
• Summer Temperature control is activated inner
Summer. Compensation occurs considering the
seasonal external temperature curve and (optional) room
dynamic compensation. During summer, in cooling mode,
the logic will consider the limitation set by the room dew
point.
• Summer: Temperature control is activated only during
the summer season. The control unit will deactivate all
the winter functions and the change of season will no
longer be enabled. Compensation occurs considering the
external temperature curve and (optional) room dynamic
compensation. The logic will consider the limitation set by
the room dew point.
STEP B: configure the type of system operation.
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ S
YSTEM
\
T
YPE
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ S
YSTEM
\ S
ETTINGS
\
C
LIMATE
SYS[1] Climate 01
──────────────────────
Type:External/Room
Season:Win + Sum:
──────────────────────
Operating climate
and season
SYS[1] Type 01
Structure:Floor
MixType:An Min-Max
00 10
MixDirRev: Sum Win
TDir TRev
──────────────────────
Type of system