39
C
ONFIGUR
ATION
SUMMER
COMPENSATION
LINE
The parameters to be entered in the screen represent the
characterisation of the compensation curve shown in the
figure below. The control unit will adjust the water delivery
temperature according to the outdoor temperature and to
the dew point.
Cooling Curve (Summer compensation).
Summer Compensation Line Reference Settings
WALL/CEILING
Name
Min
Max
Name
Val
TExt
20°C
30°C
Off.
0
Del.T
16°C
12°C
FLOOR
Name
Min
Max
Name
Val
TExt
23°C
32°C
Off.
0
Del.T
20°C
15°C
During the calculation phase, in summer operating mode, the control unit, given the measured outdoor temperature, will calculate
a temperature that we will indicate as T
MCL
, i.e., a temperature calculated through the compensation line.
30°C
Max External T. °C
20°C
Min External T. °C
12°C
Min Del. T. °C
16°C
Max Del. T. °C
T
MCL
Offset °C
“Parallel shifting”
Delivery Temp. °C
External
Temp. °C
T
MCL
= Temperature calculated through the compensation line
SYS[1] SumComp 01
──────────────────────
Min Max Off
TExt:23.0 32.0 0.0
TDel:20.0 15.0
──────────────────────
Summer compensation
curve
Path:
T
ECHNICAL
M
ENU
\ S
ETTINGS
\ S
YSTEM
\ S
ETTINGS
\
S
UMMER
COMPENSATION