When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-145
RAAA145 The Extended D-
Script has an error.
There is an error in the used
Extended Script. Check the com-
mands’ format.
)
GP-Pro EX Refer-
ence Manual
“Chapter 21 Com-
mands and Descrip-
tions” (page 21-1)
RAAA150 The provided pass-
word is incorrect.
Please enter the cor-
rect one.
The security feature’s password
input is incorrect. Confirm that the
input is correct (upper-case/lower-
case letters, etc.) and enter the pass-
word again.
)
GP-Pro EX Refer-
ence Manual
“22.4.1 Introduc-
ing the Password
Input Window”
(page 22-7)
RAAA151 Change the screen
from the host.
This appears when a screen change
occurs from the PLC (host) by the
forced screen change method (the
traditional method for a screen
change), and you cancel the dis-
played password input.
If you want to cancel, make sure to
use a cancel notification bit and
return to the previous screen from
the PLC (host).
—
RAAA152 Cannot use the COM
port.
This appears when the COM port
you are trying to use is already in use
by another feature. Check the set-
tings again.
)
GP-Pro EX Refer-
ence Manual “7.4
Changing a
Device/PLC”
(page 7-17)
RAAA153 No dictionary file
was found.
The English dictionary file does not
exist in internal storage or in the CF-
card. Transfer the project data again.
—
RAAA154 The specified filing
data cannot be used
with this project.
This appears if the designated filing
data does not match the project data
when transferring filing data from
the CF-card to SRAM. Make sure to
use filing data that matches the
project data.
)
GP-Pro EX Refer-
ence Manual “24.6
Saving Sampling
Data to CF Card/
USB storage”
(page 24-20)
RAAA155 The IP address
duplicates that of
another device.
Please change the
address of either this
machine or the other.
(IP:XXX.XXX.XXX.X
XX,MAC:XX:XX:XX:
XX:XX:XX)
*1
A machine with the same IP address
exists on the network. Change the IP
address of this machine or of the
other machine.
)
GP-Pro EX Refer-
ence Manual
“33.2.2 Transfer
Process n Trans-
fer from PC to GP
(Send)” (page 33-
6)
RAAA156 The 9th pin of the
COM port has not
been set to VCC (5V
Power Supply).
Please check your
cable or connected
equipment.
The COM port’s 9-pin could not be
set to VCC (5V power supply).
Check the COM port’s connection
cable and the machine it is con-
nected to. Then reset the machine or
verify the project’s script settings are
set to a 5V power supply.
)
Continued
Error No.
Error Message
Cause and Solution
Reference