Problems with Display operation
Maintenance/Troubleshooting
1-59
1.3.7 The screen flickers.
Is the screen redisplayed after the screen appears?
Cause
The address of [Switching Control Address] (language change function) may already be
in use.
Solution
Disable the language change function if it is not necessary. If the language change func-
tion is necessary, check if the set address is already is use.
• When the language change function is necessary
Select [Text Table Settings] from [Common Settings] of GP-Pro EX. Check if the set
address overlaps with the address of [Switching Control Address] in [Language
Change Settings].
• When the language change function is not necessary
Select [Text Table Settings] from [Common Settings] of GP-Pro EX. Uncheck [Enable
Language Change Feature] in [Language Change Settings]. Transfer the project file to
the Display.
• The default value of the start address of the system data area has the same
address as the default value of [Switching Control Address]. They may over-
lap. If so, change the address of either one of the two.