When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-110
1616
Each screen is lim-
ited to 1 Show CSV
parts (Special Data
Display.)
Make sure to only place 1
Special Data Display (CSV
display feature) on the screen.
For any others, the action may
not function correctly.
)
1618
You cannot use Edit
mode for Show
CSV parts (Special
Data Display)
drawn on Window
screens.
Make sure to use the CSV dis-
play feature of a Special Data
Display placed on a base
screen.
1619
Each screen is lim-
ited to 1 Filing part
(Special Data Dis-
play).
Make sure to only place 1
Special Data Display (File
Manager feature) on the
screen. For any others, the
action may not function cor-
rectly.
1620
You cannot use the
Filing parts (Spe-
cial Data Display)
on Window
screens.
Make sure to use the File
Manager feature of a Special
Data Display placed on a base
screen.
1621
Each screen is lim-
ited to 1 Sampling
Data Display.
Make sure to only place 1 Sam-
pling Data Display on the
screen. For any others, the action
may not function correctly.
—
1623
You cannot use Edit
mode for Sampling
Data Displays
drawn on Window
screens.
Do not use the data edit func-
tion when using the sampling
data display in the window
screen.
)
GP-Pro EX Refer-
ence Manual
“24.8.2 Sampling
Data Display Guide
n Basic Settings”
(page 24-94)
1624
Each screen is lim-
ited to 1 Historical
Data Display
Switch.
Make sure to only place 1
Switch/Lamp (Historical Data
Display feature) on the screen.
For any others, the action may
not function correctly.
)
1625
Each screen is lim-
ited to 1 Historical
Trend Graph set up
to display historical
data.
Make sure to only place 1 His-
torical Trend Graph (Historical
Data Display feature) on the
screen. For any others, the action
may not function correctly.
1626
On each screen,
you can set up a
maximum 3 win-
dows (2 if using
Global Windows)
that use Continuous
Read.
Make sure that the number of
Window parts placed on the
screen for continuous read set-
tings does not exceed 3 (2
when using Global Windows).
Any other Windows will not
function, however, up to 3
continuous read Windows and
381 common Windows can be
placed on the screen.
)
GP-Pro EX Refer-
ence Manual
“18.7.1 Bit Action”
(page 18-22)
Continued
Error
No.
Screen
ID/No./Line
Error Message
Handling method