When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-103
Data Limitation
WinGP
Error Message
Cause and Solution
Reference
Project exceeds data limit.
Unable to send the project to
the display unit. Save project
anyway?
You can save the data with the error,
but you cannot transfer it to the main
unit. Check the error contents.
)
“1.6.1 Software
(GP-Pro EX)-
related errors n
Errors displayed
during screen cre-
ation” (page 1-93)
Exceeded data history limit.
The display can use up to
768 records.
With a display other than the IPC
series, the total number of stored alarm
history events has exceeded 768 items.
(This error results from model
changeover from the IPC series.)
Reduce the total number of stored his-
tory events to 768 items or less.
)
GP-Pro EX Refer-
ence Manual
“37.1.3 Differ-
ences between IPC
and GP” (page 37-
4)
The maximum number of
registered messages has
been exceeded. The maxi-
mum number for this display
unit is 2048, including the Bit
and Word Monitoring.
With a display other than the IPC series,
the number of registered bit monitoring/
word monitoring messages has exceeded
2048 items. (This error results from
model changeover from the IPC series.)
Reduce the total number of registered
messages to 2048 items or less.
)
Error Message
Cause and Solution
Reference
Please select Items to print.
The print option is not selected. Check
the selected options and print again.
)
GP-Pro EX Refer-
ence Manual
“34.6.1 Print Set-
tings Guide n
Common” (page
34-42)
Error Message
Cause and Solution
Reference
The number of parts exceeds
the limit.
The total number of parts located on
one screen has exceeded 1,280 items.
Reduce the number of parts located on
the screen.
)
GP-Pro EX Refer-
ence Manual
“37.1.3 Differ-
ences between
IPC and GP”
(page 37-4)
Too many addresses.
The total number of addresses specified
on one screen has exceeded 3,000
items. Reduce the number of addresses
specified on the screen.
The transmission data size
exceeds the maximum limit.
Check your settings.
The total volume of project data has
exceeded the limit value.
Delete some drawings, parts and
devices from the project so that the
total data volume does not exceed the
limit value. GP3000: 8 M, IPC: 16 M
)
GP-Pro EX Refer-
ence Manual
“37.1.3 Differ-
ences between
IPC and GP”
(page 37-4)
Continued