Page 52
PARAMETERS COM 2 WHEN ETHERNET IP IS PRESENT
ENABLING FIELDBUS
Enabling the ETHERNET IP; if OFF, no error message regarding the fieldbus communication is displayed:
Selectable values:
OFF, ON
Default: OFF
IP ADDRESS
IP protocol address
ETHERNET.
Values from 0.0.0.0 to 255.255.255.255
Default: 0.0.0.0
SUBNET MASK
Mask protocol subnet
ETHERNET IP.
Values from 0.0.0.0 to 255.255.255.255
Default: 0.0.0.0
INPUT AREA
Dimension of the input area for fieldbus (values expressed in bytes).
Selectable values:
32, 64, 96, 128
Default: 128
OUTPUT AREA
Dimension of the output area for fieldbus (values expressed in bytes).
Selectable values:
32, 64, 96, 128
Default: 128
In the case of an ETHERNET IP fieldbus, the EDS configuration file “HILSCHER NIC 50-RE EIS V1.1.EDS” is
provided. The size of the input and output areas set in the PLC (default input area of 128 bytes, default
output area of 128 bytes) must match the size of the input and output areas selected in the instrument
(“INP.ADJ.” Parameters and “OUT.ADJ.”).